INTRODUCTION:-
ppt download click here https://goo.gl/SKRAvr
ppt download click here https://goo.gl/SKRAvr
Tapping's are provided on a transformer winding for selecting cutting out a certain number of turns on the transformer winding thus obtaining a variable turns ratio.
This is done in order to maintain the output voltage within desirable limits because the equipments work satisfactorily at a somewhat fixed voltage and voltage variation is a common phenomenon in the power system.
MATHEMATICAL EXPRESS:-
Suppose I have a transformer as follows:
No. of primary turns = 1000No. of secondary turns = 100
Turns ratio = 1000:100 = 10:1
Turns ratio = 1000:100 = 10:1
Now assume that the volatge has suddenly drops to 50V. I still want 10V to be available at the secondary. If cut out 500 turns from the primary, the new turns ratio will be
500:100 = 5:1
Now with 50V applied to the primary, I still get 10V at the secondary. The transformer tappings serve this purpose of cutting out the turns.
500:100 = 5:1
Now with 50V applied to the primary, I still get 10V at the secondary. The transformer tappings serve this purpose of cutting out the turns.